Minimum Configuration
For an IEC 60870-5 point to be functional (online), you need to configure these features, then put the point In Service and save the configuration:
- The Outstation on which the point is located
- The Information Object Address
- If the point is a Digital Point, the Number of Bits that make up the point
- If the point is a Digital Output Point, you need to enable the required number of control Actions.
The settings above are the minimal requirements for a functional IEC 60870-5 outstation.
If you want the Geo SCADA Expert server to store point data historically, you also need to:
- Enable and configure logging on the Historic tab if data is to be stored historically in the server database
- Enable and configure logging on the <Point Type> tab if data is to be stored historically at the outstation.