Configuring an IEC 60870-5 Phoenix PSTN Channel
For each telephone line connection that exists for communications between the Geo SCADA Expert server and the Phoenix outstations on your system, you need to configure an IEC 60870-5 Phoenix PSTN Channel item in the Geo SCADA Expert database.
You configure the properties of each channel using the fields on the IEC 60870-5 Phoenix PSTN Channel Form. The Form has several tabs.
Use the fields on the PSTN Channel tab to:
Use the fields on the Scan Parameters tab to:
- Configure the Scan Parameters—see Defining Scan Parameter Settings for a Channel in the Geo SCADA Expert Guide to Advanced Drivers.
- Specify when Communication Statistics are Updated—see Defining the Communication Statistics Update Rate in the Geo SCADA Expert Guide to Advanced Drivers.
- Specify any Pre- or Post-Ambles—see Defining any Default Pre- and Post-Amble Message Settings for a Channel in the Geo SCADA Expert Guide to Advanced Drivers.
ATTENTION: The IEC 60870-5-101 protocol uses the hexadecimal digits 68 or 10 to indicate the start of a message (or hexadecimal E5 if the system uses single character acknowledgments). As such, we advise only using hexadecimal 68, 10, or E5 as a pre-amble where such a character is required by the transmission system and is not seen by the receiving device. Hexadecimal 68, 10, and E5 should not be used for pre- or post-amble ‘padding’.
The fields on other tabs are common to channels on many advanced drivers—for information, see Tabs on Channel Forms in the Geo SCADA Expert Guide to Advanced Drivers.