Add a DNP3 Route
You add a DNP3 route for the SCADAPack device to send unsolicited events to the Geo SCADA Expert server.
To add a DNP3 route, do the following:
- Right-click the SCADAPack 575 Device Configuration item and select Edit Tables.
The table editor window is displayed. - Select the Add DNP3 Route button.
- Set the Source Port to Any Port.
- Set the Source Start address and the Source End address to 0 to match the same address that you entered for the DNP3 Outstation Address earlier in this tutorial.
- Set the Destination Start address and the Destination End address to 30000 to match the same address that you entered for the DNP3 Controlling Station Address earlier in this tutorial.
- Set the Destination Port to Ethernet 1.
- Set the Connect Number to match the IP address of the Geo SCADA Expert server.
- Set the Routing Status to On Static.
- Select the OK button to add the DNP3 route to the table.
- Save the configuration.
After adding the DNP3 route to the SCADAPack 575 device, you can proceed to Create an Analog Configuration Item.
Further Information